A study on Overvoltage and Protection of Line-Commutated Converter HVDC Metallic Return Cable

Yeuntae Yoo, Seungmin Jung, Gilsoo Jang

Research output: Contribution to journalArticle

1 Citation (Scopus)

Abstract

Metallic return cable in modern LCC HVDC system had been considered a necessary choice for newly installed projects, due to environmental concern near earth electrode. Like most of neutral cable that has been installed so far, it is unnecessary for those cables to require same specification to pole cable in the system. Usually, their voltage and current insulation limit is much lower than those of pole cables' requirement. To ensure reliable operation of HVDC system and to optimize neutral cable's insulating capability, further study on phenomena occurred on the neutral cable after fault on the system has to be measured and mitigated. In this paper, short circuit faults has been applied to LCC HVDC system, monitoring the effect on the neutral cable, and the counter measures to protect them are being considered.

Original languageEnglish
Pages (from-to)369-372
Number of pages4
JournalIFAC-PapersOnLine
Volume48
Issue number30
DOIs
Publication statusPublished - 2015

Fingerprint

Cables
Poles
Grounding electrodes
Short circuit currents
Insulation
Specifications
Monitoring
Electric potential

Keywords

  • LCC HVDC
  • Metallic return cable
  • Neutral cable
  • Overvoltage and protection

ASJC Scopus subject areas

  • Control and Systems Engineering

Cite this

A study on Overvoltage and Protection of Line-Commutated Converter HVDC Metallic Return Cable. / Yoo, Yeuntae; Jung, Seungmin; Jang, Gilsoo.

In: IFAC-PapersOnLine, Vol. 48, No. 30, 2015, p. 369-372.

Research output: Contribution to journalArticle

@article{7559eda088d04feb813c6b3c6e5cf9c1,
title = "A study on Overvoltage and Protection of Line-Commutated Converter HVDC Metallic Return Cable",
abstract = "Metallic return cable in modern LCC HVDC system had been considered a necessary choice for newly installed projects, due to environmental concern near earth electrode. Like most of neutral cable that has been installed so far, it is unnecessary for those cables to require same specification to pole cable in the system. Usually, their voltage and current insulation limit is much lower than those of pole cables' requirement. To ensure reliable operation of HVDC system and to optimize neutral cable's insulating capability, further study on phenomena occurred on the neutral cable after fault on the system has to be measured and mitigated. In this paper, short circuit faults has been applied to LCC HVDC system, monitoring the effect on the neutral cable, and the counter measures to protect them are being considered.",
keywords = "LCC HVDC, Metallic return cable, Neutral cable, Overvoltage and protection",
author = "Yeuntae Yoo and Seungmin Jung and Gilsoo Jang",
year = "2015",
doi = "10.1016/j.ifacol.2015.12.406",
language = "English",
volume = "48",
pages = "369--372",
journal = "IFAC-PapersOnLine",
issn = "2405-8963",
publisher = "IFAC Secretariat",
number = "30",

}

TY - JOUR

T1 - A study on Overvoltage and Protection of Line-Commutated Converter HVDC Metallic Return Cable

AU - Yoo, Yeuntae

AU - Jung, Seungmin

AU - Jang, Gilsoo

PY - 2015

Y1 - 2015

N2 - Metallic return cable in modern LCC HVDC system had been considered a necessary choice for newly installed projects, due to environmental concern near earth electrode. Like most of neutral cable that has been installed so far, it is unnecessary for those cables to require same specification to pole cable in the system. Usually, their voltage and current insulation limit is much lower than those of pole cables' requirement. To ensure reliable operation of HVDC system and to optimize neutral cable's insulating capability, further study on phenomena occurred on the neutral cable after fault on the system has to be measured and mitigated. In this paper, short circuit faults has been applied to LCC HVDC system, monitoring the effect on the neutral cable, and the counter measures to protect them are being considered.

AB - Metallic return cable in modern LCC HVDC system had been considered a necessary choice for newly installed projects, due to environmental concern near earth electrode. Like most of neutral cable that has been installed so far, it is unnecessary for those cables to require same specification to pole cable in the system. Usually, their voltage and current insulation limit is much lower than those of pole cables' requirement. To ensure reliable operation of HVDC system and to optimize neutral cable's insulating capability, further study on phenomena occurred on the neutral cable after fault on the system has to be measured and mitigated. In this paper, short circuit faults has been applied to LCC HVDC system, monitoring the effect on the neutral cable, and the counter measures to protect them are being considered.

KW - LCC HVDC

KW - Metallic return cable

KW - Neutral cable

KW - Overvoltage and protection

UR - http://www.scopus.com/inward/record.url?scp=84964237776&partnerID=8YFLogxK

UR - http://www.scopus.com/inward/citedby.url?scp=84964237776&partnerID=8YFLogxK

U2 - 10.1016/j.ifacol.2015.12.406

DO - 10.1016/j.ifacol.2015.12.406

M3 - Article

VL - 48

SP - 369

EP - 372

JO - IFAC-PapersOnLine

JF - IFAC-PapersOnLine

SN - 2405-8963

IS - 30

ER -