Acoustic monitoring of HV equipment with optical fiber sensor

T. Y. Kim, J. H. Nam, K. S. Suh

Research output: Contribution to conferencePaperpeer-review

1 Citation (Scopus)

Abstract

This paper presents the preliminary results on the application of optical fiber sensor (OFS) for the measurements of discharging signals in insulating oil. An all-optical-fiber-sensing system using a Mach-Zehnder interferometry technique was constructed. It was found that the discharging signal produced by needle-sphere electrodes could be detected by OFS, which was confirmed by current probe and PZT sensor. By quantification of acoustic signal measured by OFS, a correlation between acoustic and electrical discharge signals was observed.

Other

OtherProceedings of 2001 International Symp. on Electrical Insulating Materials (ISEIM 2001) / 2001 Asian Conf. on Electrical Insulation Diagnosis (ACEID 2001) / 33rd Symp. on Electrical and Electronic Insulating Materials and Applications in Systems
Country/TerritoryJapan
CityHimeji
Period01/11/1901/11/22

ASJC Scopus subject areas

  • Engineering(all)
  • Materials Science(all)

Fingerprint

Dive into the research topics of 'Acoustic monitoring of HV equipment with optical fiber sensor'. Together they form a unique fingerprint.