TY - JOUR
T1 - Constructability and heat exchange efficiency of large diameter cast-in-place energy piles with various configurations of heat exchange pipe
AU - Park, Sangwoo
AU - Sung, Chihun
AU - Jung, Kyoungsik
AU - Sohn, Byonghu
AU - Chauchois, Alexis
AU - Choi, Hangseok
N1 - Funding Information:
This research was supported by the Korea Institute of Energy Technology Evaluation and Planning (KETEP), Ministry of Knowledge Economy (Grant No. 20113030110010 and Grant No. 2013T100200057 ).
PY - 2015/11/5
Y1 - 2015/11/5
N2 - A new ground heat exchanger (GHEX) assembled in a ground source heat pump (GSHP) system has been devised, which is equipped in a structural pile, and thus called an “energy pile”. In this study, six large-diameter cast-in-place energy piles that encased various types of heat exchange pipes (i.e., three parallel U-types with 5 pairs, 8 pairs and 10 pairs; two coil-types with 200 mm coil pitch and 500 mm coil pitch; and S-type) were constructed in a test bed, and the constructability of each type of the energy pile was compared. Additionally, a 30 m-deep closed-loop vertical GHEX was separately constructed to compare the thermal performance and economic feasibility with the energy piles. A series of in-situ thermal response tests (TRTs) was performed to evaluate the relative heat exchange efficiency of each energy pile according to the various heat exchange pipe configurations. The relative heat exchange efficiency obtained in the cast-in-place energy piles and the down-sized 30 m-deep closed-loop vertical GHEX was normalized by the pile length (or borehole length) and the total heat exchange pipe length. The result from the in-situ tests indicates that the longer the heat exchange pipe installed, the higher heat exchange efficiency per pile length. However, in the case of tight layouts of the heat exchange pipe, thermal interference occurs between adjacent pipe loops, which decreases heat exchange efficiency. Economic feasibility of the energy piles was evaluated, considering the material and installation costs for assembling the heat exchange pipe with consideration of the heat exchange efficiency. It is concluded that the coil-type cast-in-place energy pile can achieve sufficient capacity for heat exchange, compared with the closed-loop vertical GHEX.
AB - A new ground heat exchanger (GHEX) assembled in a ground source heat pump (GSHP) system has been devised, which is equipped in a structural pile, and thus called an “energy pile”. In this study, six large-diameter cast-in-place energy piles that encased various types of heat exchange pipes (i.e., three parallel U-types with 5 pairs, 8 pairs and 10 pairs; two coil-types with 200 mm coil pitch and 500 mm coil pitch; and S-type) were constructed in a test bed, and the constructability of each type of the energy pile was compared. Additionally, a 30 m-deep closed-loop vertical GHEX was separately constructed to compare the thermal performance and economic feasibility with the energy piles. A series of in-situ thermal response tests (TRTs) was performed to evaluate the relative heat exchange efficiency of each energy pile according to the various heat exchange pipe configurations. The relative heat exchange efficiency obtained in the cast-in-place energy piles and the down-sized 30 m-deep closed-loop vertical GHEX was normalized by the pile length (or borehole length) and the total heat exchange pipe length. The result from the in-situ tests indicates that the longer the heat exchange pipe installed, the higher heat exchange efficiency per pile length. However, in the case of tight layouts of the heat exchange pipe, thermal interference occurs between adjacent pipe loops, which decreases heat exchange efficiency. Economic feasibility of the energy piles was evaluated, considering the material and installation costs for assembling the heat exchange pipe with consideration of the heat exchange efficiency. It is concluded that the coil-type cast-in-place energy pile can achieve sufficient capacity for heat exchange, compared with the closed-loop vertical GHEX.
KW - Closed-loop vertical ground heat exchanger
KW - Constructability of energy pile
KW - Energy pile
KW - In-situ thermal response test
KW - Relative heat exchange efficiency
UR - http://www.scopus.com/inward/record.url?scp=84930698297&partnerID=8YFLogxK
UR - http://www.scopus.com/inward/citedby.url?scp=84930698297&partnerID=8YFLogxK
U2 - 10.1016/j.applthermaleng.2015.05.044
DO - 10.1016/j.applthermaleng.2015.05.044
M3 - Article
AN - SCOPUS:84930698297
SN - 1359-4311
VL - 90
SP - 1061
EP - 1071
JO - Applied Thermal Engineering
JF - Applied Thermal Engineering
ER -