Derivation of P-Q loss sensitivities by angle reference transposition and an application to optimal P-Q generation for minimum cost

Sang Joong Lee, Seong Deog Yang

Research output: Contribution to journalArticle

10 Citations (Scopus)

Abstract

In this letter, the reactive power loss sensitivities as well as the active loss sensitivities are derived using the angle reference transposition. Four kinds of power loss sensitivities of all generators, including the slack bus, can be obtained by specifying the angle reference on a load bus that has no generation. As an example application, we show a formula with which these loss sensitivities can be used to derive the optimal P-Q allocation for minimizing the total system operating cost. A simulation is carried out on a sample system, and the results show that these loss sensitivities can also be used to obtain the optimal solutions in power system computations.

Original languageEnglish
Pages (from-to)428-430
Number of pages3
JournalIEEE Transactions on Power Systems
Volume21
Issue number1
DOIs
Publication statusPublished - 2006 Feb

Keywords

  • Angle reference transposition
  • Cost minimization
  • Loss sensitivity

ASJC Scopus subject areas

  • Energy Engineering and Power Technology
  • Electrical and Electronic Engineering

Fingerprint Dive into the research topics of 'Derivation of P-Q loss sensitivities by angle reference transposition and an application to optimal P-Q generation for minimum cost'. Together they form a unique fingerprint.