Field test of multi-functional variable refrigerant flow system

Xiaojie Lin, Hoseong Lee, Yunho Hwang, Reinhard Radermacher, Saikee Oh

Research output: Contribution to journalArticle

3 Citations (Scopus)

Abstract

In this study, a multi-functional variable refrigerant flow system operated in heat recovery mode with a water heating system was experimentally investigated. The multi-functional variable refrigerant flow system could supply space cooling, space heating, and hot water simultaneously in multiple zones. Its system performance with the water heating system operation was evaluated under a cooling main mode and a heating main mode. For the cooling main mode, when the water heating system was operated, the daily multi-functional variable refrigerant flow system performance was improved by 20.4%. This was mainly due to the increased heat recovery ratio from 0 to 0.1 and the reduced compressor pressure ratio. The pressure ratio was reduced by 16.5% because the condensing capacity was shared by both the water heating system and outdoor heat exchangers. For the heating main mode, when the water heating system was operated, the daily multi-functional variable refrigerant flow system performance was improved by 7.3%. This was mainly due to the increased part-load ratio of the system, which resulted in the increase of the compressor efficiency. The performance of the heat recovery mode between indoor units was also tested. It was found that the heat recovery operation could reduce discharge pressure by 22.2% and improve the hourly performance factor by 17%.

Original languageEnglish
Pages (from-to)648-657
Number of pages10
JournalScience and Technology for the Built Environment
Volume21
Issue number5
DOIs
Publication statusPublished - 2015 Jan 1
Externally publishedYes

Fingerprint

Flow of fluids
Heating
Waste heat utilization
Water
Cooling
Compressors
Multiple zones
Space heating
Heat exchangers

ASJC Scopus subject areas

  • Environmental Engineering
  • Building and Construction
  • Fluid Flow and Transfer Processes

Cite this

Field test of multi-functional variable refrigerant flow system. / Lin, Xiaojie; Lee, Hoseong; Hwang, Yunho; Radermacher, Reinhard; Oh, Saikee.

In: Science and Technology for the Built Environment, Vol. 21, No. 5, 01.01.2015, p. 648-657.

Research output: Contribution to journalArticle

Lin, Xiaojie ; Lee, Hoseong ; Hwang, Yunho ; Radermacher, Reinhard ; Oh, Saikee. / Field test of multi-functional variable refrigerant flow system. In: Science and Technology for the Built Environment. 2015 ; Vol. 21, No. 5. pp. 648-657.
@article{63ab3bfc8c384e6e9eb06f58a0867d19,
title = "Field test of multi-functional variable refrigerant flow system",
abstract = "In this study, a multi-functional variable refrigerant flow system operated in heat recovery mode with a water heating system was experimentally investigated. The multi-functional variable refrigerant flow system could supply space cooling, space heating, and hot water simultaneously in multiple zones. Its system performance with the water heating system operation was evaluated under a cooling main mode and a heating main mode. For the cooling main mode, when the water heating system was operated, the daily multi-functional variable refrigerant flow system performance was improved by 20.4{\%}. This was mainly due to the increased heat recovery ratio from 0 to 0.1 and the reduced compressor pressure ratio. The pressure ratio was reduced by 16.5{\%} because the condensing capacity was shared by both the water heating system and outdoor heat exchangers. For the heating main mode, when the water heating system was operated, the daily multi-functional variable refrigerant flow system performance was improved by 7.3{\%}. This was mainly due to the increased part-load ratio of the system, which resulted in the increase of the compressor efficiency. The performance of the heat recovery mode between indoor units was also tested. It was found that the heat recovery operation could reduce discharge pressure by 22.2{\%} and improve the hourly performance factor by 17{\%}.",
author = "Xiaojie Lin and Hoseong Lee and Yunho Hwang and Reinhard Radermacher and Saikee Oh",
year = "2015",
month = "1",
day = "1",
doi = "10.1080/23744731.2015.1047720",
language = "English",
volume = "21",
pages = "648--657",
journal = "Science and Technology for the Built Environment",
issn = "2374-4731",
publisher = "Taylor and Francis Ltd.",
number = "5",

}

TY - JOUR

T1 - Field test of multi-functional variable refrigerant flow system

AU - Lin, Xiaojie

AU - Lee, Hoseong

AU - Hwang, Yunho

AU - Radermacher, Reinhard

AU - Oh, Saikee

PY - 2015/1/1

Y1 - 2015/1/1

N2 - In this study, a multi-functional variable refrigerant flow system operated in heat recovery mode with a water heating system was experimentally investigated. The multi-functional variable refrigerant flow system could supply space cooling, space heating, and hot water simultaneously in multiple zones. Its system performance with the water heating system operation was evaluated under a cooling main mode and a heating main mode. For the cooling main mode, when the water heating system was operated, the daily multi-functional variable refrigerant flow system performance was improved by 20.4%. This was mainly due to the increased heat recovery ratio from 0 to 0.1 and the reduced compressor pressure ratio. The pressure ratio was reduced by 16.5% because the condensing capacity was shared by both the water heating system and outdoor heat exchangers. For the heating main mode, when the water heating system was operated, the daily multi-functional variable refrigerant flow system performance was improved by 7.3%. This was mainly due to the increased part-load ratio of the system, which resulted in the increase of the compressor efficiency. The performance of the heat recovery mode between indoor units was also tested. It was found that the heat recovery operation could reduce discharge pressure by 22.2% and improve the hourly performance factor by 17%.

AB - In this study, a multi-functional variable refrigerant flow system operated in heat recovery mode with a water heating system was experimentally investigated. The multi-functional variable refrigerant flow system could supply space cooling, space heating, and hot water simultaneously in multiple zones. Its system performance with the water heating system operation was evaluated under a cooling main mode and a heating main mode. For the cooling main mode, when the water heating system was operated, the daily multi-functional variable refrigerant flow system performance was improved by 20.4%. This was mainly due to the increased heat recovery ratio from 0 to 0.1 and the reduced compressor pressure ratio. The pressure ratio was reduced by 16.5% because the condensing capacity was shared by both the water heating system and outdoor heat exchangers. For the heating main mode, when the water heating system was operated, the daily multi-functional variable refrigerant flow system performance was improved by 7.3%. This was mainly due to the increased part-load ratio of the system, which resulted in the increase of the compressor efficiency. The performance of the heat recovery mode between indoor units was also tested. It was found that the heat recovery operation could reduce discharge pressure by 22.2% and improve the hourly performance factor by 17%.

UR - http://www.scopus.com/inward/record.url?scp=84940375582&partnerID=8YFLogxK

UR - http://www.scopus.com/inward/citedby.url?scp=84940375582&partnerID=8YFLogxK

U2 - 10.1080/23744731.2015.1047720

DO - 10.1080/23744731.2015.1047720

M3 - Article

VL - 21

SP - 648

EP - 657

JO - Science and Technology for the Built Environment

JF - Science and Technology for the Built Environment

SN - 2374-4731

IS - 5

ER -