Influence of the expansion device on the performance of a heat pump using R407C under a range of charging conditions

Jongmin Choi, Yong Chan Kim

Research output: Contribution to journalArticle

41 Citations (Scopus)

Abstract

The objective of this study is to investigate the effects of the expansion device on the performance of a water-to-water heat pump using R407C, which has been considered as one of the alternative refrigerants to replace R22 with "soft-optimization", at various charging conditions. The heat pump applying the expansion devices of a capillary tube and an EEV was tested by varying refrigerant charge amount from -20% to +20% of full charge and changing water temperature entering the condenser from 30 °C to 42 °C, while maintaining water temperature entering the evaporator at 25 °C. The R22 capillary tube system is utilized as a baseline unit for the performance comparison with the R407C system. The performance of the capillary tube system is more sensitive to off-design charge than that of the EEV system. As the refrigerant charge deviates from the full charge, the R407C EEV system shows a much lower degradation of capacity and COP as compared to the R22 and R407C capillary tube systems due to an optimum control of superheat by electronically adjusting the EEV opening. In addition, the R407C EEV system shows more a stable compressor discharge temperature at off-design charge than the R407C capillary tube system.

Original languageEnglish
Pages (from-to)378-384
Number of pages7
JournalInternational Journal of Refrigeration
Volume27
Issue number4
DOIs
Publication statusPublished - 2004 Jun 1

Fingerprint

Capillary tubes
heat pumps
water temperature
Hot Temperature
Pumps
condensers
compressors
Refrigerants
Equipment and Supplies
evaporators
Water
water
Temperature
degradation
Evaporators
temperature
Compressors
Degradation

Keywords

  • Capillary
  • Electric expansion device
  • Experiment
  • Heat pump
  • Performance
  • R407C

ASJC Scopus subject areas

  • Food Science
  • Mechanical Engineering

Cite this

Influence of the expansion device on the performance of a heat pump using R407C under a range of charging conditions. / Choi, Jongmin; Kim, Yong Chan.

In: International Journal of Refrigeration, Vol. 27, No. 4, 01.06.2004, p. 378-384.

Research output: Contribution to journalArticle

@article{313daec06195405ca84f7bb1c7249522,
title = "Influence of the expansion device on the performance of a heat pump using R407C under a range of charging conditions",
abstract = "The objective of this study is to investigate the effects of the expansion device on the performance of a water-to-water heat pump using R407C, which has been considered as one of the alternative refrigerants to replace R22 with {"}soft-optimization{"}, at various charging conditions. The heat pump applying the expansion devices of a capillary tube and an EEV was tested by varying refrigerant charge amount from -20{\%} to +20{\%} of full charge and changing water temperature entering the condenser from 30 °C to 42 °C, while maintaining water temperature entering the evaporator at 25 °C. The R22 capillary tube system is utilized as a baseline unit for the performance comparison with the R407C system. The performance of the capillary tube system is more sensitive to off-design charge than that of the EEV system. As the refrigerant charge deviates from the full charge, the R407C EEV system shows a much lower degradation of capacity and COP as compared to the R22 and R407C capillary tube systems due to an optimum control of superheat by electronically adjusting the EEV opening. In addition, the R407C EEV system shows more a stable compressor discharge temperature at off-design charge than the R407C capillary tube system.",
keywords = "Capillary, Electric expansion device, Experiment, Heat pump, Performance, R407C",
author = "Jongmin Choi and Kim, {Yong Chan}",
year = "2004",
month = "6",
day = "1",
doi = "10.1016/j.ijrefrig.2003.12.002",
language = "English",
volume = "27",
pages = "378--384",
journal = "International Journal of Refrigeration",
issn = "0140-7007",
publisher = "Elsevier Limited",
number = "4",

}

TY - JOUR

T1 - Influence of the expansion device on the performance of a heat pump using R407C under a range of charging conditions

AU - Choi, Jongmin

AU - Kim, Yong Chan

PY - 2004/6/1

Y1 - 2004/6/1

N2 - The objective of this study is to investigate the effects of the expansion device on the performance of a water-to-water heat pump using R407C, which has been considered as one of the alternative refrigerants to replace R22 with "soft-optimization", at various charging conditions. The heat pump applying the expansion devices of a capillary tube and an EEV was tested by varying refrigerant charge amount from -20% to +20% of full charge and changing water temperature entering the condenser from 30 °C to 42 °C, while maintaining water temperature entering the evaporator at 25 °C. The R22 capillary tube system is utilized as a baseline unit for the performance comparison with the R407C system. The performance of the capillary tube system is more sensitive to off-design charge than that of the EEV system. As the refrigerant charge deviates from the full charge, the R407C EEV system shows a much lower degradation of capacity and COP as compared to the R22 and R407C capillary tube systems due to an optimum control of superheat by electronically adjusting the EEV opening. In addition, the R407C EEV system shows more a stable compressor discharge temperature at off-design charge than the R407C capillary tube system.

AB - The objective of this study is to investigate the effects of the expansion device on the performance of a water-to-water heat pump using R407C, which has been considered as one of the alternative refrigerants to replace R22 with "soft-optimization", at various charging conditions. The heat pump applying the expansion devices of a capillary tube and an EEV was tested by varying refrigerant charge amount from -20% to +20% of full charge and changing water temperature entering the condenser from 30 °C to 42 °C, while maintaining water temperature entering the evaporator at 25 °C. The R22 capillary tube system is utilized as a baseline unit for the performance comparison with the R407C system. The performance of the capillary tube system is more sensitive to off-design charge than that of the EEV system. As the refrigerant charge deviates from the full charge, the R407C EEV system shows a much lower degradation of capacity and COP as compared to the R22 and R407C capillary tube systems due to an optimum control of superheat by electronically adjusting the EEV opening. In addition, the R407C EEV system shows more a stable compressor discharge temperature at off-design charge than the R407C capillary tube system.

KW - Capillary

KW - Electric expansion device

KW - Experiment

KW - Heat pump

KW - Performance

KW - R407C

UR - http://www.scopus.com/inward/record.url?scp=1642603365&partnerID=8YFLogxK

UR - http://www.scopus.com/inward/citedby.url?scp=1642603365&partnerID=8YFLogxK

U2 - 10.1016/j.ijrefrig.2003.12.002

DO - 10.1016/j.ijrefrig.2003.12.002

M3 - Article

VL - 27

SP - 378

EP - 384

JO - International Journal of Refrigeration

JF - International Journal of Refrigeration

SN - 0140-7007

IS - 4

ER -